Home › Products

Eleven formulations, five product groups.

Developed and manufactured by Kuvars Kimya since 2003. Alkaline coil cleaning, inhibitor-enhanced descaling and neutralisation, molybdate- and phosphate-based protection, microbial control and leak sealing. 1 kg, 25 kg and 1000 kg IBC. Technical data sheet for every product.

NANO CLEAN, 25 kg jerrycanNANO CLEAN, 1000 kg IBC

All products

Selection rule

Copper, aluminium and mixed-metal systems → NANO CLEAN. Steel and cast iron → NANO CLEAN 100. After every acidic cleaning → NANO CLEAN NR. Closed loops → NANOSAFE X. Steam boilers → NANOSAFE X 100. Steam in contact with food → NANOSAFE X 200 HAL. Chiller, AHU and fancoil circuits → NANOSAFE X 300. Cooling towers → NANOSAFE X 400 DC on treated water. Microbial and biofilm control → NANOSAFE BIOCID. Micro-leaks → WTR RESIST.

Find the right chemistry for your system

System or problemProductNote
Fouled AC coils, AHU or fancoil surfaces (dust, oil, biofilm)CLIMA CLEARAlkaline coil cleaner, 1:3–1:10
Scale in copper, aluminium or mixed-metal exchangers, boilers, condenser tubesNANO CLEAN → NANO CLEAN NRInhibitor-enhanced descaler, then neutralisation
Scale and rust in steel or cast-iron boilers, steam generators, pipelinesNANO CLEAN 100 → NANO CLEAN NRIndustrial acidic cleaner, then neutralisation
New installation before start-upNANO CLEAN → NANO CLEAN NRTwo-step pre-commissioning flushing
Closed-loop heating, cooling or hot water circulation (no boiling)NANOSAFE XMolybdate-based, 0.3–0.6 L/m³, continuous
Steam boiler or steam generator, non-food-contact steamNANOSAFE X 100Molybdate-based, 0.3–0.6 L/m³; also closed-loop heating
Steam that may contact food or dairy productsNANOSAFE X 200 HALFormulated in compliance with FDA criteria, 0.3–0.5 L/m³
Chiller, AHU and fancoil water circuitsNANOSAFE X 300Phosphate-based three-in-one, 0.3–0.5 L/m³
Open-circuit cooling tower and tower-connected exchangers, heavy foulingNANOSAFE X 400 DCMolybdate-based dispersant, 0.2–0.4 L/m³, treated water
Bacteria, algae, biofilm in cooling towers and process waterNANOSAFE BIOCIDIsothiazolinone-based, shock or continuous
Micro-leaks in piping, pools, terraces, subfloorsWTR RESISTSilicate-based sealer, circulated

Describe your system and we will review it.

Send the system type, metal, volume and the problem you see. Our technical team replies within 24 hours on business days.